Mitsubishi Electric AE-200A Service Handbook page 42

Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

[IV Product specifications and functions]
Item
Unit information
Items common to the AE-200/AE-50/EW-50 unit and Web browser
(Basic system)
The unit name, ID number, whether expand system, date display format, time display format,
temperature display format, room temperature display, pressure display format, and sensor display
format (occupancy, lighting, and humidity) show/hide settings can be set.
AE-200/AE-50 unit only
The display language (Japanese, English, French, German, Spanish, Italian, Russian, Chinese, or
Portuguese) can be changed and the LCD screen brightness, volume, whether test run usable, and
whether screen lock function usable can be set.
Web browser only
The list screen group name display and filter sign show/hide settings can be set.
Network settings
The IP address, subnet mask, and gateway settings of the LAN of the AE-200/AE-50/EW-50, the
M-NET address related to M-NET, local remote controller operation prohibited range settings,
external input settings, and external I/O settings can be set.
Advanced settings
The time master/sub, ON/OFF of old model compatible mode, and enable/disable of schedule
season settings can be set.
Group settings
Register indoor units, LOSSNAY, general equipment, remote controllers, and sub system controllers
to a group.
Block settings
Register set groups to a block.
Note: A block that spans AE-200/AE-50/EW-50 systems cannot be set.
Interlock LOSSNAY
Register indoor units to interlocked LOSSNAY as interlocking sources.
settings
Floor layout settings
The basic floor settings, group display location settings, and floor plan settings can be set.
Error mail settings
Various settings such as the e-mail server and error e-mail send address for using error mail
notification can be set.
Peak cut control
Settings such as the control system or the control method of indoor units and outdoor units for using
settings
peak cut control can be set.
*2
Measurement settings
The settings of the temperature sensor and humidity sensor of the AI controller and the settings of
the electricity meter, water supply meter, etc. of the PI controller can be set.
Set temperature range
The temperature range of each remote controller can be set for when limiting the operation range of
limit setting
the set temperature of local remote controllers.
Note: The range for which monitoring operation is possible differs depending on the model. This
Energy management
The external temperature sensor, apportioning mode, and the electricity meter of the apportioning
settings*2
source can be set.
Night mode schedule
The time period for operation in night mode can be set for when using the night mode (low-noise
settings
operation) of outdoor units.
Note: This cannot be used with Mr. Slim and room air conditioners.
Changeover settings
The operation mode (cooling/heating) of all indoor units connected to the same outdoor unit can be
switched based on changes in the room temperature. (Other than the R2 series) The outdoor unit for
which to switch between cooling and heating and the changeover mode (auto/representative group)
can be set.
External temperature
The external temperature sensor unit can be selected and the control level can be set for each group
interlock control
for using the external temperature interlock control function.
Setback function
Set the control period setting and the upper limit temperature and lower limit temperature for each
group for using the setback function.
Interlock control *2
Perform interlock control between connected equipment with interlocking conditions set.
(Up to 150 interlocking conditions can be registered for each AE-200/AE-50/EW-50.)
Note: Interlock control that spans AE-200/AE-50/EW-50 systems cannot be performed.
Maintenance user
The maintenance user name and password can be set.
Building manager
The building manager (administrator user) name and password and the available functions can be
(administrator user)
set.
Data backup
The setting data, user information, and other data can be saved.
Data loading
The setting data can be loaded.
CSV output
The operation data (charge parameters and power consumption data) for up to 62 days when the
data type is 1-day intervals and up to 4 days when the data type is 30-minute intervals can be saved
to a USB memory device.
Energy management
The energy management data can be output.
data output
Note: The data needs to be output from each AE-200/AE-50/EW-50.
cannot be used with A control models (Mr. Slim), room air conditioners, and residential air
conditioners.
Description
38