[VI Q & A]

[5] About models other than air-conditioning units

No.
1
LOSSNAY
Can OA Processing unit and LOSSNAY be set to the
same group?
2
OA
Is the humidification operation possible when the
Processing
operation mode is cooling?
unit
3
LOSSNAY,
Can the night purge setting also be set for
OA
LOSSYNAY and OA Processing units without the
Processing
night purge function?
unit
4
LOSSNAY,
There is a 24-hour ventilation setting menu. Can it be
OA
set?
Processing
unit
5
CAHV
Can a CAHV air source heat pump be connected?
6
CRHV
Can a CRHV water source heat pump be connected?

[6] Other

No.
Question
1
Is the controller to use different for
managing 50 units or less and 200 units
or less?
2
Can the TG-2000A be connected with a
mixture of AE-200/AE-50/EW-50 and
G-150AD or G(B)-50?
3
If the power of the
AE-200/AE-50/EW-50 is cut because
of, for example, a power failure, how
long will the backup data be retained?
Question
50 units or less: AE-200 or EW-50
From 51 to 200 units: AE-200 (with M-NET connection) + AE-50/EW-50 (1 to 3 units)
From 51 to 200 units: AE-200 (without M-NET connection) + AE-50/EW-50 (2 to 4
units)
In the case of 51 to 200 units, it is necessary to add a HUB, change the wiring
connections, etc.
Yes, it can.
The TG-2000A that supports AE-200/AE-50/EW-50 is Ver.6.60 or later.
When the TG-2000A is connected with a mixture of AE-200/AE-50/EW-50, the
maximum number of indoor units that can be targets for operation and monitoring is
2,000.
The current time is backed up for about one week and is then reset (2014/04/01).
The settings are retained but there are data retention periods.
For example, the period is 62 days in the case of billing data and 24 months in the
case of energy usage status data.
When a retention period elapses, the data is overwritten.
87
Answer
Yes they can be set to the same group but their functions
differ so set them to different groups.
No, it is not. It is only possible in the heating mode.
No, it cannot. It can only be set for equipment with the
night purge function.
No, it cannot.
Yes.
Yes.
Answer