[III System restrictions and notes]
(5) Operation block setting restrictions
・ An operation block is a collection of groups, and groups of different models (air-conditioning units, LOSSNAY, general equipment,
etc.) can even be set in the same operation block.
・ An operation block that spans AE-200/AE-50/EW-50 systems cannot be set.
・ The operation items differ so we recommend setting operation blocks separately for each of the indoor units, LOSSNAY units,
and A-control models.
・ When peak-cut control is used, blocks become the setting target unit so be sure to set the operation blocks.
(6) Energy management block setting restrictions
・ An energy management block is a collection of operation blocks and OA Processing unit (with interlock control), and operation
blocks of different models (air-conditioning units, LOSSNAY, general equipment, etc.) can also be set in the same energy
management block.
HUB
LAN
AE-200
LAN
EW-50
・ An energy management block that spans multiple AE-50/EW-50 in an AE-200 system can be set, but an energy management
block cannot span multiple AE-200 systems.
・ When the apportioned electricity billing function is used, energy management blocks become the apportioning target unit so be
sure to set the energy management blocks.
(7) Group setting restrictions
Restrictions also apply to group settings.
Item
Number of remote controllers
that can be connected
Number of indoor units that can
be connected in one group
Number of SC and RC units
that can be connected in one
group
Number of groups per area
Number of groups per floor
*1
An ME remote controller and MA remote controller cannot be used together in the same group.
*2
If a group is made up of indoor units with different functions, only the function of the indoor unit with the lowest address in the
group is operated and monitored.
Description
Up to two remote controllers in one
group
1 to 16
Up to four units in one group
Up to 30 groups per area
Up to 180 groups per floor
MA remote controllers do not need to be registered and set on this equipment.* 1
IC, AIC, FU, and LC cannot be connected to the same group.
However, groups that span multiple AE-200/AE-50/EW-50 cannot be configured.* 2
9
Group
Operation
block
Operation block
OA Processing unit
(with interlock control)
management
Remark
[Area]
Up to 30 groups can be placed
[Floor]
Up to 180 groups can be placed
Group
Energy
block