(2) Number of connectible/controllable units in a system
1.
Number of controllable units for AE-200/AE-50/EW-50
Item
Number of controllable
indoor units
[Code] IC: Indoor unit (OA Processing unit [without interlock control]), LC: Free-plan LOSSNAY,
FU: OA Processing unit (with interlock control), AIC: Mr. Slim air conditioner, RAC: Room air conditioner,
PWFY: Air To Water (PWFY), HWHP: HWHP (CAHV, CRHV)
*1
AE-50 cannot be operated individually.
*2
One contact is counted as one unit for a DIDO controller.
*3
Maximum number of connectible/controllable units in the case of AHC: Indoor units + AHC = 70 units.
2.
Number of controllable units in an AE-200 + expansion controller (AE-50/EW-50) system
Item
Number of controllable
indoor units
*1
When M-NET of AE-200 is not used or the apportioned electricity billing function of AE-200 is used, four AE-50/EW-50 units can
be connected. (Max. 200 indoor units)
*2
One contact is counted as one unit for a DIDO controller.
*3
Maximum number of connectible/controllable units in the case of AHC: Indoor units + AHC = 70 units.
(3) When performing integrated centralized control with the integrated centralized control software TG-2000A.
Use Ver.6.60 or later of TG-2000A.
(4) Number of connectable units
The table below summarizes the number of connectable units in an M-NET system.
Indoor units, PWFY, HWHP, LOSSNAY, OA Processing unit, DIDO
controllers, PI controllers*1, and AI controllers per AE-200/AE-50/EW-50
AHC per AE-200/AE-50/EW-50
Indoor units, PWFY, HWHP, LOSSNAY, OA Processing unit, and DIDO
controllers in one group
AHC in a group
Remote controllers in a group
System controllers in a group
(AE-200/AE-50/EW-50 included)
LOSSNAY unit that can be interlocked with each indoor unit
Indoor units that can be interlocked with each LOSSNAY unit
*1
15 PI controllers can be connected to each AE-200/AE-50/EW-50 and a maximum of 20 can be connected within an AE-200 system.
A PI is counted as one unit.
*2
By connecting AE-50/EW-50 controllers to an AE-200, up to 200 units can be controlled.
*3
The maximum number of controllable units for DIDO controllers differs depending on the number of channels used.
*4
One contact of a DIDO controller is calculated as one unit.
Description
Max. 50 *1
Description
Max. 200 (When using three
AE-50/EW-50)*1
Unit type
Managed equipment
IC, LC, FU, AIC, RAC, PWFY, HWHP,
AI controllers, PI controllers, DIDO controllers*2, AHC*3
Managed equipment
IC, LC, FU, AIC, RAC, PWFY, HWHP, AI controllers, PI
controllers, DIDO controllers*2, AHC*3
Number of connectable units
Up to 50 units*2 (including the interlocked LOSSNAY units)
Maximum of 70 indoor units for indoor units+AHC
1–16 units*3*4
(Indoor units, PWFY, HWHP, LOSSNAY, OA Processing unit, and
DIDO controllers cannot be used together in the same group.)
1 unit
(At least one indoor unit is required in the same group.)
0–2 units
0–5 units
(Up to four remote and system controllers combined can be
assigned to each group.)
1 unit
1–16 units