8 Output Assemblies (Drive Consumes)
u
Extended Speed Control Output - 21 (0x15)
Output
Word
Instance
0
21
1
Name
Forward Run Command
Run Fwd
0: Stop
1: Forward Run
Reverse Run Command
Run Rev
0: Stop
1: Reverse Run
Fault Reset
Fault Reset
(0 to 1 transition: Fault Reset)
Run command from Network
NetCtrl
0: Depends on b1-02
1: Enables the run command from network
Speed reference from Network
NetRef
0: Depends on b1-01
1: Enables the speed reference from network
Speed Command
Sets drive speed reference.
Speed reference data: Frequency reference/2
Speed Reference
Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/2
Unit depends on o1-03.
36
Byte
Bit 7
Bit 6
0
NetRef
1
2
3
YASKAWA TOEP YAICOM 15A V1000 Option Dual-Port EtherNet/IP SI-EN3D/V Installation Manual
Bit 5
Bit 4
NetCtrl
Speed Reference (Low Byte)
Speed Reference (High Byte)
Description
SS
(SS: Speed scale)
2
= 1024 = 0x0400 Hex
Bit 3
Bit 2
Bit 1
Fault
Run
Reset
Rev
Bit 0
Run
Fwd