YASKAWA v1000 Installation Manual page 33

Ethernet/ip
Hide thumbs Also See for v1000:
Table of Contents

Advertisement

<4>
Cycle power for setting changes to take effect.
<5>
When F7-13 is set to 0, parameters F7-01 to F7-12 must be set, and all IP Addresses (as defined with parameters
F7-01 to F7-04) must be unique.
<6>
When F7-14 is set to 0 or 2, parameter F7-15 must be set.
<7>
Default setting differs depending on drive software version. PRG: 1012 to 1015: 0
PRG: 1016 and later: 1
<8>
Setting range differs depending on drive software version. PRG: 1012 to 1023, Range: 0 to 2
PRG: 1024 and later, Range: 0 to 8
<9>
Setting values differ depending on drive software version. PRG: 1012 to 1015, Default: 0; Range: 0, 10, 100
PRG: 1016 to 1023, Default: 10; Range: 10, 100
PRG: 1024 and later, Default: 10; Range: 10; 100 to 102
No.
Name
U6-80
to
Online IP Address
U6-83
U6-84
to
Online Subnet
U6-87
U6-88
to
Online Gateway
U6-91
U6-92 Online Speed
U6-93 Online Duplex
U6-94 Port 2 Duplex
U6-95 Port 2 Speed
U6-98 First Fault
U6-99 Current Fault
YASKAWA TOEP YAICOM 15A V1000 Option Dual-Port EtherNet/IP SI-EN3D/V Installation Manual
Table 8 Option Monitors
Description
IP Address currently available; U6-80 is the most significant
octet
Subnet currently available; U6-84 is the most significant octet 0 to 255
Gateway currently available; U6-88 is the most significant
octet
Link Speed
Duplex Setting
Port 2 Duplex Setting
Port 2 Link Speed
First Option Fault
Current Option Fault
6 Related Drive Parameters
Value Range
0 to 255
0 to 255
10: 10 Mbps
100: 100 Mbps
0: Half, 1: Full
0: Half, 1: Full
10: 10 Mbps
100: 100 Mbps