Parameter
Explanation
Set Point Deviation
10.22
Level
Detection Time of
10.23
Set Point Deviation
Level
Offset Level of
10.24
Liquid Leakage
Liquid Leakage
10.25
Change Detection
Time Setting for
10.26
Liquid Leakage
Change
10.27
|
Reserved
10.33
Fault Codes
Fault
Fault Descriptions
Name
Over current
Abnormal increase in current.
Low voltage
The AC motor drive detects that
the DC bus voltage has fallen
below its minimum value.
Over voltage
The DC bus voltage has
exceeded its maximum
allowable value.
22
ADV20 QS, V1.02
Settings
0 to 100%
0 to 9999 sec
0 to 50%
0 to 100% (0: disable)
0.1 to 10.0 sec (0: disable)
1.
Check if motor power corresponds with the AC
motor drive output power.
2.
Check the wiring connections to U/T1, V/T2,
W/T3 for possible short circuits.
3.
Check the wiring connections between the AC
motor drive and motor for possible short
circuits, also to ground.
4.
Check for loose contacts between AC motor
drive and motor.
5.
Increase the Acceleration Time.
6.
Check for possible excessive loading
conditions at the motor.
7.
If there are still any abnormal conditions when
operating the AC motor drive after a short-
circuit is removed and the other points above
are checked, it should be sent back to
manufacturer.
1.
Check whether the input voltage falls within the
AC motor drive rated input voltage range.
2.
Check whether the motor has sudden load.
3.
Check for correct wiring of input power to R-S-T
(for 3-phase models) without phase loss.
1.
Check if the input voltage falls within the rated
AC motor drive input voltage range.
2.
Check for possible voltage transients.
3.
DC-bus over-voltage may also be caused by
motor regeneration. Either increase the Decel.
Time or add an optional brake resistor (and
brake unit).
4.
Check whether the required braking power is
within the specified limits.
Factory
Setting
0
10
0
0
0.5
Corrective Actions