Parameter
Explanation
05.12
13th Step Speed
Frequency
05.13
14th Step Speed
Frequency
05.14
15th Step Speed
Frequency
Over-Voltage Stall
06.00
Prevention
Over-Current Stall
06.01
Prevention during
Accel
Over-Current Stall
06.02
Prevention during
Operation
Over-Torque
06.03
Detection Mode
(OL2)
Over-Torque
06.04
Detection Level
Over-Torque
06.05
Detection Time
Electronic Thermal
06.06
Overload Relay
Selection
Electronic Thermal
06.07
Characteristic
Present Fault
06.08
Record
06.09
Second Most
Recent Fault Record
Italiano
0.00 to 600.0 Hz
0.00 to 600.0 Hz
0.00 to 600.0 Hz
Group 6 Protection Parameters
115/230V series: 330.0V to 410.0V
460V series: 660.0V to 820.0V
0.0: Disable over-voltage stall prevention
0:Disable
20 to 250%
0:Disable
20 to 250%
0: Disabled
1: Enabled during constant speed operation.
After the over-torque is detected, keep
running until OL1 or OL occurs.
2: Enabled during constant speed operation.
After the over-torque is detected, stop
running.
3: Enabled during accel. After the over-
torque is detected, keep running until OL1 or
OL occurs.
4: Enabled during accel. After the over-
torque is detected, stop running.
10 to 200%
0.1 to 60.0 sec
0: Standard motor (self cooled by fan)
1: Special motor (forced external cooling)
2: Disabled
30 to 600 sec
0: No fault
1: Over current (oc)
2: Over voltage (ov)
3: IGBT Overheat (oH1)
4: Reserved
5: Overload (oL)
6: Overload1 (oL1)
7: Motor over load (oL2)
8: External fault (EF)
9: Current exceeds 2 times rated current
during accel.(ocA)
10: Current exceeds 2 times rated current
during decel.(ocd)
11: Current exceeds 2 times rated current
English
Settings
ADV20 QS, V1.02
Factory
NOTE
Setting
0.00
0.00
0.00
390.0V
780.0V
170
170
0
150
0.1
2
60
0
17