gefran ADV20 series Quick Start-Up page 53

Compact v/f ac drive 0.4 to 3.7 kw 115-230 vac 1ph, 230-460 vac 3ph
Table of Contents

Advertisement

Available languages

Available languages

Parameter
Explanation
Input Terminal for
10.01
PID Feedback
Proportional Gain
10.02
(P)
10.03
Integral Time (I)
Derivative Control
10.04
(D)
Upper Bound for
10.05
Integral Control
Primary Delay Filter
10.06
Time
PID Output Freq
10.07
Limit
PID Feedback
10.08
Signal Detection
Time
Treatment of the
10.09
Erroneous PID
Feedback Signals
Gain Over the PID
10.10
Detection Value
Source of PID Set
10.11
point
10.12
PID Feedback Level 1.0 to 50.0%
Detection Time of
10.13
PID Feedback
Sleep/Wake Up
10.14
Detection Time
10.15
Sleep Frequency
10.16
Wakeup Frequency
Minimum PID
10.17
Output Frequency
Selection
PID Control
10.18
Detection Signal
Reference
PID Calculation
10.19
Mode Selection
Treatment of the
10.20
Erroneous PID
Feedback Level
Restart Delay Time
10.21
after Erroneous PID
Deviation Level
Italiano
0: Positive PID feedback from external
terminal AVI (0 ~ +10VDC)
1: Negative PID feedback from external
terminal AVI (0 ~ +10VDC)
2: Positive PID feedback from external
terminal ACI (4 ~ 20mA)
3: Negative PID feedback from external
terminal ACI (4 ~ 20mA)
0.0 to 10.0
0.00 to 100.0 sec (0.00=disable)
0.00 to 1.00 sec
0 to 100%
0.0 to 2.5 sec
0 to 110%
0.0 to 3600 sec (0.0 disable)
0: Warn and RAMP to stop
1: Warn and COAST to stop
2: Warn and keep operation
0.0 to 10.0
0.00 to 600.0Hz
0.1 to 300.0 sec
0.0 to 6550 sec
0.00 to 600.0 Hz
0.00 to 600.0 Hz
0: By PID control
1: By minimum output frequency (Pr.01.05)
1.0 to 99.9
0: Series mode
1: Parallel mode
0: Keep operating 1: Coast to stop 2: Ramp
to stop 3: Ramp to stop and restart after time
set in Pr.10.21
1 to 9999 sec
English
Settings
ADV20 QS, V1.02
Factory
NOTE
Setting
0
1.0
1.00
0.00
100
0.0
100
60.0
0
1.0
0.00
10.0
5.0
0.0
0.00
0.00
0
99.9
0
0
60
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents