Application Programming
LD
Variable
Run1
BOOL
ManCtl1
BOOL
StartAT1
BOOL
PV1
REAL
SP1
REAL
OprSetParams1
_sOPR_SET_PARAMS
InitSetParams1
_sINIT_SET_PARAMS
PB1
REAL
TI1
TIME
TD1
TIME
ManMV1
REAL
ATDone1
BOOL
ATBusy1
BOOL
Error1
BOOL
ErrorID1
WORD
MV1
REAL
PulseOnTime
TIME
PulseCycTime
TIME
ResetPulse
BOOL
PIDAT_instance
PIDAT
TOF_instance
TOF
TON_instance
TON
Obtain the process value.
Inline ST
1 PV1:=INT_TO_REAL(AI1)/REAL#10.0;
Execute PIDAT instruction.
Run1
Run
ManCtl1
ManCtl
StartAT1
StartAT
PV1
PV
SP1
SP
OprSetParams1
OprSetParams
InitSetParams1
InitSetParams
ProportionalBand
PB1
IntegrationTime
TI1
DerivativeTime
TD1
ManMV
ManMV1

NJ-series Instructions Reference Manual (W502)

Data type
False
False
False
0.0
90
(MVLowLmt:=0.0, MVUpLmt:=100.0,
ManResetVal:=0.0, MVTrackSw:=False,
MVTrackVal:=0.0, StopMV:=0.0,
ErrorMV=0.0, Alpha:=0.65,
ATCalcGain:=1.0, ATHystrs:=0.2)
(SampTime:=T#100ms, RngLowLmt:=0.0,
RngUpLmt:=1000.0, DirOpr:=False)
10
T#0S
T#0S
0.0
False
False
False
16#0
0.0
T#0s
T#1s
False
// Convert PV AI1 to real number.
// CJ1W-PH41U output is ten times the process value, so divide by 10.0.
PIDAT_instance
PIDAT
ATDone
ATBusy
ATBusy1
Error
Error1
ErrorID1
ErrorID
MV
MV1
PB1
TI1
TD1
ManMV1
Retain
Initial value
ATDone1
2 Instruction Descriptions
Comment
Execution condition
Manual/auto control
Autotuning execution condition
Process value
Set point
Operation setting parameters
Initial setting parameters
Proportional band
Integration time
Derivative time
Manual manipulated variable
Autotuning normal completion
Executing autotuning
Error
Error ID
Manipulated variable
Control output ON time
Control period
Timer reset
2
2-415