TON_instance[0]
TON_instance[1]
:
TON_instance[9]
TON_instance[10]
:
TON_instance[99]
LD
Variable
Input
TimeUp
TimePT
TON_instance
i
UINT#0
UINT#99
UINT#1
Input[i]
TimePT[i]
NEXT
EN ENO
ST
Variable
Input
TimeUp
TimePT
TON_instance
i
FOR i:=0 TO 99 DO
TON_instance[i](
In := Input[i],
PT:= TimePT[i],
Q =>TimeUp[i]);
END_FOR;
NJ-series Instructions Reference Manual (W502)
1s
TimeUp[0]
TRUE
2s
TimeUp[1]
TRUE
:
:
10s
TimeUp[9]
TRUE
0s
TimeUp[10]
TRUE
:
:
0s
TimeUp[99]
TRUE
Data type
ARRAY[0..99] OF BOOL
ARRAY[0..99] OF BOOL
ARRAY[0..99] OF TIME
ARRAY[0..99] OF TON
UINT
FOR
EN
ENO
InitVal
Index
i
EndVal
StepVal
TON_instance[i]
TimeUp[i]
TON
In
Q
PT
ET
Data type
ARRAY[0..99] OF BOOL
ARRAY[0..99] OF BOOL
ARRAY[0..99] OF TIME
ARRAY[0..99] OF TON
UINT
Initial value
[100(False)]
[100(False)]
[T#1s, T#2s, T#3s, T#4s, T#5s, T#6s,
T#7s, T#8s, T#9s, T#10s, 90(T#0s)]
0
Initial value
[100(False)]
[100(False)]
[T#1s, T#2s, T#3s, T#4s, T#5s, T#6s,
T#7s, T#8s, T#9s, T#10s, 90(T#0s)]
0
2 Instruction Descriptions
Comment
Timer input
Timer output
Set time
Index
Comment
Timer input
Timer output
Set time
Index
2
2-119