2 Instruction Descriptions

CTUD

The CTUD instruction creates an up-down counter that operates according to an up-counter input and a
down-counter input. The preset value and counter value must have an INT data type.
Instruction
CTUD
Up-down Counter
Variables
Name
Meaning
CU
Up-counter
input
CD
Down-
counter
input
Reset
Reset
signal
Load
Load signal
PV
Preset
value
QU
Up-counter
output
QD
Down-
counter
output
CV
Counter
value
Bit string
CU
OK
CD
OK
Reset
OK
Load
OK
2-142
Name
FB/FUN
FB
I/O
Description
Up counter input
Down counter input
TRUE: Reset CV to 0.
Input
TRUE: CV set to PV.
The final counter value
when operating as an up
counter
The initial counter value
when operating as a down
counter
TRUE: up-counter output
ON
FALSE: up-counter output
OFF
TRUE: down-counter output
Output
ON
FALSE: down-counter out-
put OFF
Counter present value
Graphic expression
CTUD_instance
CTUD
CU
QU
CD
QD
Reset
CV
Load
PV
Valid range
Depends on data type.
0 to 32767
Depends on data type.
0 to 32767
Integers
NJ-series Instructions Reference Manual (W502)
ST expression
CTUD_instance (CU, CD,
Reset, Load, PV, QU, QD,
CV);
Unit
Default
FALSE
---
0
---
---
Times, durations,
dates, and text strings

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nj501-1300Nj501-1400

Table of Contents