Cipucmmread - Omron NJ501-1500 Reference Manual

Machine automation controller nj-series
Hide thumbs Also See for NJ501-1500:
Table of Contents

Advertisement

2 Instruction Descriptions

CIPUCMMRead

The CIPUCMMRead instruction uses a UCMM explicit message to read the value of a variable in
another Controller on the specified CIP network.
Instruction
Name
CIPUCMM
Read Variable
Read
UCMM Explicit
Variables
Name
Meaning
RoutePath
Route path
TimeOut
Timeout time
SrcDat
Source vari-
able name
Size
Number of
elements to
read
DstDat
Read data
RcvSize
Read data
size
Bit strings
RoutePath
TimeOut
SrcDat
Size
OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK
DstDat
An enumeration, array, structure, structure member, or union member can also be specified.*
RcvSize
* You cannot specify a STRING array.
2-706
FB/
Graphic expression
FUN
FB
CIPUCMMRead_instance
CIPUCMMRead
Execute
RoutePath
TimeOut
SrcDat
Size
DstDat
I/O
Description
Route path
Timeout time
Name of variable to read in
Input
other Controller
Number of elements to read
In-out
Read data value
Output
Read data size
Integers
OK
OK
OK
OK
CIPUCMMRead_instance(Execute,
RoutePath, TimeOut, SrcDat, Size,
DstDat, Done, Busy, Error, ErrorID,
Done
ErrorIDEx, RcvSize);
Busy
Error
ErrorID
ErrorIDEx
RcvSize
Valid range
Depends on data
type.
1 to 65535
Depends on data
type.
0 to 496
Depends on data
type.
0 to 496
NJ-series Instructions Reference Manual (W502)
ST expression
Unit
Default
---
---
0.1 s
20 (2 s)
''
---
1
---
---
Bytes
---
Times, durations,
dates, and text strings
OK
OK

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nj501-1300Nj501-1400

Table of Contents