Customer Monitoring
An alarm for Sync Control Trouble from the Powerware Fixed Master Sync Control
is provided to the single Powerware 9315 module system or Powerware Hot
Sync-Capacity System as Building Alarm number 4. The alarm is activated for the
following conditions:
•
Failure of one or both power supplies
•
PLC Mode switch in STOP position
•
PLC shutdown due to fatal program error.
If the Sync Control Trouble alarm activates, contact Customer Service.
NOTE: If either slave system or master system is taken out of service for
maintenance, voltage input to one of the power supplies is lost, and the Sync
Control Trouble alarm activates. The alarm clears when the UPS or SBM
system is placed back into service. Customer Service need not be
contacted.