Powerware 9315 Installation & Operation Manual page 47

Fixed master sync control
Hide thumbs Also See for 9315:
Table of Contents

Advertisement

SINGLE MODULE 30- -500 POWERWARE 9315 UPS SYSTEM CONTROL WIRING
From
UPS System
(Master)
TB6--5
TB6--6
TB6--11
TB6--12
TB6--13
Install the following jumpers, if not connected,
on UPS module terminal block TB6 when
installing the Fixed Master Sync Control:
From
TB6--5
TB6--6
TB6--7
SINGLE MODULE 750kVA POWERWARE 9315 UPS SYSTEM CONTROL WIRING
From
UPS System
(Master)
CUSTTB2--
CUSTTB2--
CUSTTB2--5
CUSTTB2--6
CUSTTB2--7 (*)
(*) Requires installation of CK155011--100 to have 750kVA module as master for any other
Powerware 9315 system other than another 750kVA unit.
Install the following jumpers, if not connected,
on UPS module terminal block CUSTTB2
when installing the Fixed Master Sync Control:
From
CUSTTB2--1
CUSTTB2--2
Field Wiring Requirements:
S Minimum insulation rating: 600 volts
S Use 14 AWG wiring for interconnections between
the Sync Control and the UPS modules.
S Install using Class 1 wiring methods.
Powerware 9315 Fixed Master Sync Control
164201325 Rev. A 060203
INTERCONNECTIONS
To Sync Control
TB1--10
BYPASS REFERENCE
BYPASS REFERENCE
TB1--11
TB1--7
TB1--8
TB1--9
To
TB6--8
TB6--9
TB6--10
INTERCONNECTIONS
To Sync Control
TB1--10
BYPASS REFERENCE
BYPASS REFERENCE
TB1--11
TB1--7
TB1--8
TB1--9
To
CUSTTB2--3
CUSTTB2--4
Description
VOLTAGE
SYNC VOLTAGE
SYNC VOLTAGE
Description
VOLTAGE
SYNC VOLTAGE
SYNC VOLTAGE
DESCRIPTION:
Table 3 -- Powerware System Control
Wiring Interconnections (Master)
DRAWING NO:
164201325---11
Remarks
Twist Together
Twist Together
Twist Together
Twist Together
Remarks
Twist Together
Twist Together
Twist Together
Twist Together
SHEET:
1 of 2
A ---19