Powerware 9315 Installation & Operation Manual page 46

Fixed master sync control
Hide thumbs Also See for 9315:
Table of Contents

Advertisement

POWERWARE 9315 UPS HOT SYNC-CAPACITY SYSTEM CONTROL WIRING
From Slave SBM
(refer to dwg
164201325- -2)
TB4--3
TB4--4
TB6--1
TB6--2
TB6--3
TB6--7
TB6--8
TB6--9
TB6--4
TB6--5
TB6--6
TB3--3
TB3--4
TB3--1
TB3--2
Note: Sync Control dry contacts are
rated at 5---30 VDC/250 VAC at 2A
per contact (maximum load).
Field Wiring Requirements:
S Minimum insulation rating: 600 volts
S Use 14 AWG wiring for interconnections between
the Sync Control and the UPS modules.
S Install using Class 1 wiring methods.
A ---18
INTERCONNECTIONS
To Sync Control
(refer to dwg
164201325- -1)
TB1--1
UPS ON BYPASS
UPS ON BYPASS
TB1--2
TB1--4
TB1--5
BYPASS VOLTAGE
BYPASS VOLTAGE
TB1--6
TB1--13
TB1--14
LOAD VOLTAGE
LOAD VOLTAGE
TB1--15
TB1--16
TB1--17
REFERENCE VOLTS
REFERENCE VOLTS
TB1--18
TB1--22
BYPASS DISABLED
BYPASS DISABLED
TB1--23
TB1--26
TB1--27
Description
PLC FAILURE
PLC FAILURE
ALARM
DESCRIPTION:
Table 2 -- Powerware Hot Sync-Capacity UPS System
Control Wiring Interconnections (Slave)
DRAWING NO:
164201325---10
Remarks
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
SHEET:
Powerware 9315 Fixed Master Sync Control
164201325 Rev. A 060203
1 of 1