Remote Monitoring; Remote Shutdown - Powerware Ferrups FE/QFE UPS User Manual

500 va–18 kva,50 and 60 hz
Table of Contents

Advertisement

Command
Short
Form
systemtest
stst
time
t
unshutup
u
*If you change parameter 39 to "Yes," this command requires a User password.

Remote Monitoring

Alarm Signal Contacts:
250 mA) that change status on any alarm condition or when the UPS is
turned off. Contacts that close on an alarm are available between Pins 23
and 24. Contacts that open on an alarm are available between Pins 24
and 25.
Inverter On Signal Contacts:
and 250 mA) that change status when the inverter turns on. Contacts
that close on inverter operation are available between Pins 12 and 13.
Contacts that open on inverter operation are available between Pins 11
and 13.
NOTE FE 500 VA–3.1 kVA models with serial numbers 25000 and greater have
equivalently rated DC solid state switches.

Remote Shutdown

The FERRUPS UPS can be connected to a remote shutdown switch to
shut off output from the UPS to your protected equipment. The
shutdown switch must have a set of contacts that can apply the UPS's
+12 Vdc on Pin 6 to the UPS's Pin 21. (You can use Pin 18 instead of
Pin 6;
connect the switch to the UPS pins. A connection between Pins 6 and 21
(or 18 and 21) shuts down UPS output power to the protected
equipment.
When the UPS Remote Shutdown feature has been activated, the UPS is
in the Off mode and the Emergency Power Off alarm sounds. A control
panel or a terminal connected to the UPS displays "Emergency PwrOff."
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) User's Guide
Password
Function
None*
Starts a system test of the logic, inverter and battery.
None
Shows the current UPS time. To set the time, enter
the command.
None
Turns audible alarm back on.
These are relay contacts (rated at 25 Vac/Vdc and
These are relay contacts (rated at 25 Vac/Vdc
.) Use a shielded, single twisted-pair cable to
do not use Pin 14