Powerware 9315 Installation & Operation Manual page 45

Fixed master sync control
Hide thumbs Also See for 9315:
Table of Contents

Advertisement

SINGLE MODULE 750kVA POWERWARE 9315 UPS SYSTEM CONTROL WIRING
From Slave UPS
(refer to dwg
164201325- -2)
CUSTTB1--1
CUSTTB1--2
CUSTTB2--1
CUSTTB2--2
CUSTTB2--5
CUSTTB2--6
CUSTTB2--3
CUSTTB2--4
CUSTTB--6*
CUSTTB--7*
CUSTP2--4
CUSTT2--5
* CUST TB located in Inverter Cabinet #2
Remove the following jumpers, if connected,
from UPS module terminal block TB6 when
installing the Sync Control:
From
CUSTTB2--1
CUSTTB2--2
Field Wiring Requirements:
S Minimum insulation rating: 600 volts
S Use 14 AWG wiring for interconnections between
the Sync Control and the UPS modules.
S Install using Class 1 wiring methods.
Powerware 9315 Fixed Master Sync Control
164201325 Rev. A 060203
INTERCONNECTIONS
To Sync Control
(refer to dwg
164201325- -1)
TB1--1
TB1--2
TB1--4
TB1--5
TB1--13
TB1--14
TB1--16
REFERENCE VOLTAGE
REFERENCE VOLTAGE
TB1--17
TB1--22
TB1--23
TB1--26
TB1--27
CAUTION
To
CUSTTB2--3
CUSTTB2--4
Description
UPS ON BYPASS
UPS ON BYPASS
(24VDC)
BYPASS VOLTAGE
BYPASS VOLTAGE
(480VAC)
LOAD VOLTAGE
LOAD VOLTAGE
(480VAC)
(480VAC)
BYPASS DISABLED
BYPASS DISABLED
(24VDC)
PLC FAILURE ALARM
PLC FAILURE ALARM
(24VDC)
DESCRIPTION:
Table 1 -- Single Module Powerware 9315 UPS System
Control Wiring Interconnections (Slave)
DRAWING NO:
Remarks
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
Twist Together
SHEET:
164201325---9
2 of 2
A ---17