6.2.6 Zero pressure calibration

Parameter
Zero pressure calibration trigger POS9
Zero pressure calibration trigger QBM #1
Zero pressure calibration trigger QBM #2
A6V10733786_en_c
Above information is available for all ebm-papst Modbus fans with interface version
>= 5.0.
Error and warning codes are shown as decimal value, for example error code '17'.
They must be converted into a bit string, for example '0000 0000 0001 0001'.
According to EBM Papst documentation, this means FB (General fan fault) and
PHA (Phase error).
When using a Modbus fan, both fans must be Modbus fans.
Both devices (POS9.., QBM97..) have integrated pressure sensors and
therefore also inbuilt zero-pressure-calibration mechanisms.
To perform calibration, all pressure hoses must be disconnected and exposed
to the same ambient pressure.
The calibration process can be manually initiated by activating the calibration
parameter.
Available parameters
BACnet object
ZePClbTrgPos9
MVAL, 628
ZePClbTrgQbm
MVAL, 638
ZePClbTrgQbm(2)
MVAL, 790
Engineering of communicative devices
Modbus components
R/RW
Note
RW
1: Ready
2: Trigger (initiates calibration)
RW
1: Ready
2: Trigger (initiates calibration)
RW
1: Ready
2: Trigger (initiates calibration)
6
153 | 170