Prn-6F Printer Installation - Honeywell MRP-2002 Instruction Manual

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

ANN-BUS Devices
Setting Printer Options
Refer to the documentation supplied with the PRN-7 printer for instructions on using the printer
menu controls. Set the printer options (under the menu area) as shown in the following table:

PRN-6F Printer Installation

When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the event
occurred. It provides 80 columns of data on standard 9" x 11" tractor-feed paper. This section con-
tains information on connecting a printer to the control panel and setting the printer options.
Connecting PRN-6F Printer
Remote printers require a primary AC power source. If required for the fire alarm system configu-
ration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power
source (battery backup). Since a secondary power source is not provided as a standard feature, a
separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency
power supply may be used, as long as it meets the power continuity requirements of NFPA 72.
Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable.
One end of the cable will plug into the DB-25 connector on the PRN-6F printer and the other end
plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB-9 port on the
ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel
printer cable. Connect either a serial or parallel printer, but not both at the same time.
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Option
Setting
Font
HS Draft
LPI
ESC Character
Bidirectional Copy
CG-TAB
Graphic
Country
E-US ASCII
Auto CR
Color Option
Not Installed
Formien
Lines
6LPI=60
Standard
Exec 10.5
Barcode
Barcode
Unsecured
Table 2.2 PRN-7 Setup Options
Option
CPI
6 LPI
Skip
ESC
Emulate
ON
I/O
Buffer
Serial
OFF
Baud
Format
Protocol
Character Set
SI.Zero
Off
Auto LF
Installation
Setting
10CPI
0.5
LQ-2550
64K
9600 or 2400
7 Bit, Even, 1 Stop
XON/XOFF
Standard
On
On
43