NFPA 72 Auxiliary Fire Alarm System
C.1 NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1.
3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2.
Cut JP30 on the MRP-2002 main circuit board to supervise placement of 4XTMF module and
circuit.
3.
Cut JP24 on the MRP-2002 main circuit board to enable FACP Supervisory relay.
4.
Refer to "4XTMF Municipal Box Transmitter Option Module" on page 33 for detailed
information.
Polarities shown in alarm condition
Figure C.2 Municipal Box Connected to 4XTMF Transmitter Module
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
NFPA Standard-Specific Requirements
Municipal Box Circuit