Master Programming Level

View Events

Pressing 1 while viewing the History Screen will allow the user to select the events to be viewed as
illustrated in the following:
While displaying the View Events screen, press 1 to view all events, 2 to view only alarms or 3 to
view other events. Use the up and down arrow keys to scroll through all of the displayed events.

Erase History

The Erase History option allows a user to erase all events from the history file. This will provide a
clean slate in order to use the history file to track future events. Pressing 2 while viewing the
History Screen will display the following screen:
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. After
the History file has been erased, the display will return to the History Screen.
3.5.9 Walktest
PROGRAMMING
Walktest allows an individual to test the fire alarm system without the necessity to reset the control
1=ANN-BUS
2=HISTORY
panel after each device activation. Pressing 3 while viewing the Programming Screen #3 will cause
3=WALKTEST
the following Walktest options to be displayed:
Programming Screen #3
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the
following screen will be displayed:
The user can now perform a one-person walktest by activating devices throughout the system. As
each device is activated, the screen will display the information about the activated device as shown
below. Note that the colon (:) in the time is replaced with an asterisk (*) to distinguish the walktest
screen from an actual alarm screen.
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
View Events Screen
ERASE HISTORY
PROCEED ?
1=YES
2=NO
Erase History Screen
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW EVENTS
Walktest Screen
UNIT IN WALKTEST
Walktest Active Screen
ALARM ZONE 1
<ADJ> <NOUN>
Z01
1000A 010805
Programming