3: Output Circuits; Enabled - Honeywell MRP-2002 Instruction Manual

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

Programming
the characters 1, A and B. Press the right arrow key to move the cursor one position to the right and
repeat the process to enter the next character. To enter a space, press the * (QZ) key four times until
a blank appears in the desired position. When all characters have been entered, press the Enter key
to store the information. The display will return to the Edit Detector Screen #5, displaying the new
information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the
first letter of the Description, Adjective or Noun field as follows:
As an example, the user could quickly enter 'FLR_3_ROOM_305' as follows:
1.
2.
3.
4.
3.5.3 Output Circuits
PROGRAMMING
The options for the Output Circuits on the control panel main circuit board can be configured by
1=FACP CONFIG
pressing 2 while viewing Programming Screen #2. The following screens will be displayed:
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
The Output Circuits can be configured independently by pressing 1 for Output 1, 2 for Output 2, 3
for Output 3 or, on the next screen, 1 for Output 4.
To program an Output circuit, press the number corresponding to the Output to be programmed.
The following screens will be displayed for each selection:

1=ENABLED

2=TYPE
Enabled
NAC #
1=ENABLED
Pressing 1 while viewing Output Screen #1 will cause the display to change to Enabled No. This
2=TYPE
ALARM NAC
will prevent the selected main circuit board NAC from activating its devices. Each press of the 1
NAC Screen #1
key will cause the display to toggle between Enabled Yes and Enabled No.
58
If the zero key is pressed, a 0 is placed in the first letter position
If the zero key is then pressed a second time with no intervening key actions, the entire field is
replaced with the field entered for the previous device programmed, and the cursor moves to
the last character of the field (Recall function). The Recalled Adjective or Noun field may now
be changed letter-by-letter
If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a 0. If the last character goes from 9 to 0 and the characters to the left of the last
character are also numbers, they are also incremented (overflow)
The above increment function may be repeated with each press of the zero key
The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3.
With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field.
With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305.
Press the Enter key to store the information.
OUTPUT CIRCUITS
1=OUTPUT 1
2=OUTPUT 2
3=OUTPUT 3
NAC Selection Screen
OUTPUT #
YES
RELEASE CIR 1
UNSUPV SHORTS
Output Screen #1
OUTPUT CIRCUITS
1=OUTPUT 4
NAC Selection Screen
OUTPUT #
1=SILENCE
N/A
2=AUTO SILENCE
N/A
3=SIL INHIBIT
NO
Output Screen #2
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Master Programming Level
OUTPUT #
1=CODING
N/A
Output Screen #3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mrp-2002eMrp-2002c

Table of Contents