FACP Configuration Templates
Device Installation Example for Template 6
Output Circuit #2
Alarm NAC
Output
Circuit #1
Release
Solenoid 1
Notes:
1.
All End-of-Line Resistors, illustrated in this example, are 4.7KΩ, ½ watt (PN: 71252).
2.
All devices are connected as Class B circuits. For details on connecting as Class A circuits,
refer to "CAC-5X Class A Converter Module" on page 31.
118
Input Circuit #1
2-Wire Smoke
Input Circuit #2
2-Wire Smoke
Input Circuit #3
Manual Release
Input Circuit #4
Abort Switch
Input Circuit #5
Discharge Pressure
Template 6: Single Hazard - Cross-Zone NAC
Output
Circuit #3
Release
Stage
Pre-
Discharge
NAC
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Output
Circuit #4
Release
Stage
Discharge
NAC
Input Circuit
#6
Supervisory