2.5 Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-lim-
ited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter
and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is illus-
trated below.
*Note: In certain applications, an NAC (power-limited circuit) could be adjacent to a
Power-limited Circuits
(Class 2)
AC Power
120 VAC
Hot (L1)
Ground
Neutral (L2)
ground
stud
Figure 2.12 Typical UL Power-limited Wiring Requirements
30
releasing circuit (nonpower-limited without supervision kit REL-4.7K)
Nonpower-limited Circuits*
CAC-5X
Agent Releasing FACP
Power-limited Circuits (Class 2)
CAC-5X
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Power-limited Wiring Requirements