B.11: Template 11: Agent/Waterflow - Cross-Zone - Honeywell MRP-2002 Instruction Manual

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

Template 11: Agent/Waterflow - Cross-Zone
B.11 Template 11: Agent/Waterflow - Cross-Zone
OUTPUT CIRCUITS
#1 RELEASE CIRCUIT 1
#2 RELEASE CIRCUIT 2
#3 ALARM NAC
#4 RELEASE STAGE
CODED
Table Legend:
* = shows relationship only, will not activate a release circuit
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xc = cross-zone output where X indicates a direct correlation between Input Zone and Output Cir-
cuit (input zone activation will activate the corresponding output circuit) and c indicates that the
output circuit will indicate when one or more inputs of a cross-zoned group have been activated
(refer to Cross Zone in "Cross-Zone for Release Circuit 1 or Release Circuit 2:" on page 61).
Cn = cross-zone inputs where n is the number of the Release Circuit. All inputs with the same
Release Circuit number must be active at the same time to turn on the corresponding Release output
circuit.
Xr = release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and r indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
"Release Stage/NAC Operation" on page 85).
Input Zone Types:
Zone 1 = circuit with type code of 2-wire smoke
Zone 2 = circuit with type code of 2-wire smoke
Zone 3 = circuit with type code Manual Release/Abort Switch Combo - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to "Abort Type" on page 65)
Zone 4 = circuit with type code of Discharge Pressure Switch
Zone 5 = circuit with type code of Waterflow
Zone 6 = circuit with type code of Supervisory
Output Circuit Types:
Output 1 = Release Circuit 1 - Supervised for shorts
Output 2 = Release Circuit 2 - Supervised for shorts
Output 3 = Alarm NAC - silenceable, programmed for Cross-Zone Pre-Discharge coded
operation for Release Circuit 1 (refer to "Cross-Zone for Release Circuit 1 or Release Circuit
2:" on page 61)
Output 4 = Release Stage Coded - nonsilenceable, programmed Release Stage Coded operation
for Release Circuit 1 (refer to "Cross-Zone for Release Circuit 1 or Release Circuit 2:" on
page 61)
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Template 11: Agent/Waterflow - Cross-Zone
1
2
MANUAL
2-WIRE
2-WIRE
RELEASE/ABORT
SMOKE
SMOKE
SW. COMBO
C1
C1
C2
C2
Xc
Xc
Xr
Xr
INPUT ZONES
3
4
DISCHARGE
WATERFLOW
PRESSURE
X
X*
X
X*
X
Xr
Xr
FACP Configuration Templates
5
6
SUPERVISORY
X
131

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mrp-2002eMrp-2002c

Table of Contents