Template 9: Dual Hazard - Cross-Zone
B.9 Template 9: Dual Hazard - Cross-Zone
OUTPUT CIRCUITS
#1 RELEASE CIRCUIT 1
#2 RELEASE CIRCUIT 2
#3 HORN NAC
#4 HORN NAC
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xc = cross-zone output where X indicates a direct correlation between Input Zone and Output Cir-
cuit (input zone activation will activate the corresponding output circuit) and c indicates that the
output circuit will indicate when one or more inputs of a cross-zoned group have been activated
(refer to "Cross-Zone for Release Circuit 1 or Release Circuit 2:" on page 61).
Cn = cross-zone inputs where n is the number of the Release Circuit. All inputs with the same
Release Circuit number must be active at the same time to turn on the corresponding Release output
circuit.
Input Zone Types:
Zone 1 = circuit with type code of 2-wire smoke
Zone 2 = circuit with type code of 2-wire smoke
Zone 3 = circuit with type code Manual Release/Abort Switch Combination - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to "Abort Type" on page 65)
Zone 4 = circuit with type code of 2-wire smoke
Zone 5 = circuit with type code of 2-wire smoke
Zone 6 = circuit with type code Manual Release/Abort Switch Combination - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to "Abort Type" on page 65)
Output Circuit Types:
Output 1 = Release Circuit 1 - Supervised for shorts
Output 2 = Release Circuit 2 - Supervised for shorts
Output 3 = Horn NAC - silenceable, programmed Cross-Zone coding operation for Release
Circuit 1 (refer to "Cross-Zone for Release Circuit 1 or Release Circuit 2:" on page 61)
Output 4 = Horn NAC - silenceable, programmed Cross-Zone coding operation for Release
Circuit 2 (refer to "Cross-Zone for Release Circuit 1 or Release Circuit 2:" on page 61)
Timers
Pre-Discharge Delay: Release 1 - set for 30 seconds; Release 2 - set for 30 seconds
Discharge: Release 1 - set for Always On; Release 2 - set for Always On
Waterflow Delay Timer - set for 90 seconds
AC Loss Delay Timer - set for 2 hours
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Template 9: Dual Hazard - Cross-Zone
1
2
2-WIRE
2-WIRE
RELEASE/ABORT
SMOKE
SMOKE
SW. COMBO
C1
C1
Xc
Xc
INPUT ZONES
3
4
MANUAL
2-WIRE
SMOKE
X
C2
X
Xc
FACP Configuration Templates
5
6
MANUAL
2-WIRE
RELEASE/ABORT
SMOKE
SW. COMBO
C2
X
Xc
X