Programming
This screen allows the user to program a specific delay time before the releasing circuit begins an
agent release during an alarm condition. A flashing cursor is positioned in the lower left corner of
the display. Enter a Pre-Discharge delay time consisting of two digits, such as 05 for five seconds.
Upon entering the second digit, the time delay will be stored in the control panel memory and the
display will return to the Delay Screen which will indicate the new Pre-Discharge delay time. In
this example, when the corresponding agent releasing circuit is activated, it will delay agent release
for five seconds.
Note that if a Manual Release is activated, the Discharge Delay time will be ignored and the
release will begin immediately.
Discharge Timer
There are two Discharge timers which allows each releasing circuit to be programmed with
different discharge delay times. The Discharge Timers determine how long an agent release will
continue once activated. The factory default setting for the Discharge Timers is Always On. To
program the Discharge Timer, press 3 for Discharge 1 while viewing the Timer Screen #1 or press 1
for Discharge 2 while viewing Timer Screen #2. The following display will appear:
Pressing 1 while viewing the Discharge Setup screen will program the releasing circuit to continue
an agent release until the panel is reset.
Pressing 2 while viewing the Discharge Setup screen will cause the following screen to be
displayed:
A Discharge Time of 01 to 20 minutes can be programmed. A flashing cursor is positioned in the
lower left corner of the display. Enter a Discharge time consisting of two digits, such as 05 for five
minutes. Upon entering the second digit, the time will be stored in the control panel memory and
the display will return to the Delay Screen which will indicate the new Discharge time. In this
example, when the corresponding agent releasing circuit is activated, it will continue an agent
release for five minutes after activation.
Note that if a Manual Release is activated, the Discharge Timer will be activated and the release
will continue for the duration of the Discharge Timer.
Waterflow Delay
TIMER
1=PRE-DISCHARGE1 030
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-
2=PRE-DISCHARGE2 030
3=DISCHARGE1
1MIN
in delays of the waterflow device. The factory default setting for Waterflow delay is 00 for no
Timer Screen #1
delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow
delay, press 3 while viewing Timer Screen #1 to display the following screen:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay
will be stored in the control panel memory and the display will return to the Delay Screen which
will indicate the new delay time.
66
DISCHARGE
1=ALWAYS ON
2=ENTER MINUTES
Discharge Setup Screen
DISCHARGE
RANGE 01-20 MINUTES
Pre-Discharge Setup Screen
WATERFLOW DELAY
RANGE 00-90 SECONDS
Waterflow Delay Screen
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016