Honeywell MRP-2002 Instruction Manual page 126

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

FACP Configuration Templates
FACP Operation
Input Zone 1 (2-Wire Smoke) Activation only:
Output 3 (Horn NAC) will pulse 1 second on, 1 second off.
Input Zone 2 (2-Wire Smoke) Activation only:
Output 3 (Horn NAC) will pulse 1 second on, 1 second off.
Input Zone 3 (Manual Release) Activation only:
Output 1 (Release Circuit 1) agent release remains on until reset.
Output 3 (Horn NAC) will turn on steady.
Input Zone 3 (Abort Release Switch) Activation only:
Pre-Discharge Timer for Release Circuit 1will continue to count down until it reaches 10
seconds and then stop. Releasing the Abort Release Switch will allow the Pre-Discharge Timer
to continue its count down from 10 second. If the Abort Release Switch is again activated
before the Pre-Discharge Timer reaches 0, the Timer will reset to 10 seconds and hold.
Input Zone 4 (2-Wire Smoke) Activation:
Output 4 (Horn NAC) will pulse 1 second on, 1 second off.
Input Zone 5 (2-Wire Smoke) Activation:
Output 4 (Horn NAC) will pulse 1 second on, 1 second off.
Input Zone 6 (Manual Release) Activation only:
Output 2 (Release Circuit 2) agent release remains on until reset.
Output 4 (Horn NAC) will turn on steady.
Input Zone 6 (Abort Release Switch) Activation only:
Pre-Discharge Timer for Release Circuit 2 will continue to count down until it reaches 10
seconds and then stop. Releasing the Abort Release Switch will allow the Pre-Discharge Timer
to continue its count down from 10 second. If the Abort Release Switch is again activated
before the Pre-Discharge Timer reaches 0, the Timer will reset to 10 seconds and hold.
Input Zone 1 (2-Wire Smoke) and Input Zone 2 (2-Wire Smoke) Activation together:
In addition to the individual events that will occur for each Input Zone as detailed above, the
Pre-Discharge Timer for Release Circuit 1 will begin to count down. Output 3 will pulse 1/2
second on, 1/2 second off while the Pre-Discharge Timer is counting down. When the Pre-
Discharge Timer reaches 0, Output 1 (Release Circuit 1) will begin the agent release which
will continue until reset. Output 3 will turn on steady when the release begins.
Input Zone 4 (2-Wire Smoke) and Input Zone 5 (2-Wire Smoke) Activation together:
In addition to the individual events that will occur for each Input Zone as detailed above, the
Pre-Discharge Timer for Release Circuit 2 will begin to count down. Output 4 will pulse 1/2
second on, 1/2 second off while the Pre-Discharge Timer is counting down. When the Pre-
Discharge Timer reaches 0, Output 2 (Release Circuit 2) will begin the agent release which
will continue until reset. Output 4 will turn on steady when the release begins.
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay (Latching) - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (2-Wire
Smoke) or Zone 3 (Manual Release) or Zone 4 (2-Wire Smoke) or Zone 5 (2-Wire Smoke) or
Zone 6 (Manual Release) will operate Alarm Relay
Trouble Relay (Tracking) - any system trouble will activate the Trouble Relay
Supervisory (Tracking) - the disabling of Releasing Circuit or any other system supervisory
will operate the Supervisory Relay
126
Template 9: Dual Hazard - Cross-Zone
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mrp-2002eMrp-2002c

Table of Contents