B.1: Template 1: Cross-Zone System - With Horn - Honeywell MRP-2002 Instruction Manual

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

Template 1: Cross-Zone System - With Horn
B.1 Template 1: Cross-Zone System - With Horn
OUTPUT CIRCUITS
#1 RELEASE CIRCUIT 1
#2 HORN NAC
#3 ALARM NAC
#4 ALARM NAC
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
Xc = cross-zone output where X indicates a direct correlation between Input Zone and Output Cir-
cuit (input zone activation will activate the corresponding output circuit) and c indicates that the
output circuit will indicate when one or more inputs of a cross-zoned group have been activated
(refer to "Cross-Zone for Release Circuit 1 or Release Circuit 2:" on page 61).
Cn = cross-zone inputs where n is the number of the Release Circuit. All inputs with the same
Release Circuit number must be active at the same time to turn on the corresponding Release output
circuit.
Input Zone Types:
Zone 1 = circuit with type code of 2-wire smoke
Zone 2 = circuit with type code of 2-wire smoke
Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release
Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Type
operation (refer to "Abort Type" on page 65)
Zone 5 = circuit with type code of Pull Station
Zone 6 = circuit with type code of Supervisory
Output Circuit Types:
Output 1 = Release Circuit 1 - Unsupervised for shorts
Output 2 = Horn NAC - silenceable, programmed for cross-zone coded operation for Release
Circuit 1 (refer to Cross Zone in the section titled "Coded NAC Operation" on page 85
Output 3 = Alarm NAC - silenceable, coded for steady on
Output 4 = Alarm NAC - silenceable, coded for steady on
Timers
Pre-Discharge Delay - set for 30 seconds
Discharge - set for 1 minute
Waterflow Delay Timer - set for 90 seconds
AC Loss Delay Timer - set for 2 hours
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Template 1: Cross-Zone System with Horn
1
2
2-WIRE
2-WIRE
SMOKE
SMOKE
C1
C1
Xc
Xc
X
X
INPUT ZONES
3
4
MANUAL
ABORT
RELEASE
STATION
X
X
X
X
FACP Configuration Templates
5
6
PULL
SUPERVISORY
X
X
101