Honeywell MRP-2002 Instruction Manual page 124

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

FACP Configuration Templates
Device Installation Example for Template 8
Output Circuit #2
Alarm NAC
Output
Circuit #1
Release
Solenoid 1
Notes:
1.
All End-of-Line Resistors, illustrated in this example, are 4.7KΩ, ½ watt (PN: 71252).
2.
All devices are connected as Class B circuits. For details on connecting as Class A circuits,
refer to "CAC-5X Class A Converter Module" on page 31.
124
Input Circuit #1
2-Wire Smoke
Input Circuit #2
2-Wire Smoke
Input Circuit #3
Manual Release
Input Circuit #4
Abort Switch
Input Circuit #5
Discharge Pressure
Template 8: Single Hazard, Single Detector - Bell/Horn/Strobe
Output
Circuit #3
Release
Stage
Coded
NAC
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Output
Circuit #4
Release
Stage
Discharge
NAC
Input Circuit
#6
Supervisory

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mrp-2002eMrp-2002c

Table of Contents