Appendix D: Facp With Keltron - Honeywell MRP-2002 Instruction Manual

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

Appendix D: FACP with Keltron

The following figure illustrates the connections between the FACP and Keltron
Receiver/Transmitter.
CAUTION:
!
FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON
MODULES ARE NOT SHOWN IN ACTUAL ORDER. FOLLOW KELTRON MANUAL AND MODULE
MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE DAMAGE.
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
Keltron 95M3158 TTM-RPS
1.
Terminals 7 and 8: Remote station alarm/trouble inputs
2.
Terminals 9 and 10: Sprinkler supervisory input
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
OBSERVE CORRECT TERMINAL LOCATIONS
UL-Listed
Sprinkler Supervisory
Signal
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Fire Alarm Control Panel
(terminal blocks are not shown in their actual
positions in order to clarify wiring connections)
UL-Listed
Alarm/Trouble
Signal
4XTMF Module
*Note: For more
information, refer to the
Keltron manual.
147