Programming
SYSTEM SETUP
1=CANADIAN OPTION

Secondary ANN-BUS Option

2=SEC ANN ENABLE
System Setup Screen #3
Pressing 2 while viewing System Setup Screen #3 allows the user to enable the secondary
ANN-BUS. The secondary ANN-BUS must be enabled if any modules are connected to the
ANN-SEC option card at J13. To enable the Secondary ANN-BUS, press 1 while viewing the
SEC-ANN screen so that the display reads SEC ANN Enabled Yes. Each press of the 1 key will
cause the display to toggle between SEC ANN Enabled Yes and SEC ANN Enabled No. The factory
default setting is ANN-SECONDARY Enabled No.
3.5.7 ANN-BUS
PROGRAMMING
Optional ANN-BUS devices available for the FACP include annunciators, relay modules and
1=ANN-BUS
2=HISTORY
printer connection for acquiring hardcopy printouts of panel data. Pressing 1 while viewing
3=WALKTEST
Programming Screen #3 will cause the control panel to display the following screens.
Programming Screen #3
An ANN-S/PG Printer module, ANN-80 LCD annunciator module and ANN-RLY relay module
can be programmed into the FACP. These devices communicate with the FACP over the ANN-BUS
terminals on the control panel.

ANN-BUS Enabled

The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads ANN-
BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANN-BUS
Enabled Yes and ANN-BUS Enabled No.

ANN-BUS Modules

If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select ANN-
BUS addresses for the module(s). The following screen will be displayed.
Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1 - 8. Pressing the number corresponding to the desired address will display a screen
with technical information about the selected module.
70
Any allowed zone type programmed as Auto-Resettable will be changed to latching version of
that zone type (N.O. Contact AR will be changed to N.O. Contact, Combo with AR
Supervisory will be changed to Combo, 2-wire Heat AR will be changed to 2-wire Heat, Low
Pressure AR will be changed to Low Pressure, High Pressure AR will change to High Pressure
and Supervisory AR will change to Supervisory)
The auto-silence feature will be disabled by the panel.
The installer must write in the Date of Final Assembly on the Master Marking and Warranty
label, located on the FACP backbox door
When the ANN-80C LCD Canadian Indicator is installed: Local Silence button will silence
annunciator piezos, Lamp Test button will perform an annunciator lamp test, pressing and
holding Sounder Test button will sound annunciator piezo, pressing step up/down arrows will
scroll through stored events. These buttons may be enabled or disabled by programming.
ANN-BUS
1=BUS ENABLED
2=BUS MODULES
3=AUTO CONFIGURE
ANN-BUS Screen #1
ANN-BUS
1=ANN-S/PG OPTIONS
NO
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-BUS MODULES
1=ADDR. 1
NONE
2=ADDR. 2
NONE
3=ADDR. 3
NONE
ANN-BUS Module Screen #1
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016