Programming
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen,
press the number key corresponding to the relay to be programmed. The following screen will
appear:
Pressing 1 will display the available relay types. Following is a list of the available programming
options for each relay:
Press 2 to select Latching or non-Latching relay. Each press of the 2 key will cause the display to
toggle between Latching Yes and No.
3.5.8 History
PROGRAMMING
The History option allows an authorized user to view or erase events which have occurred in the
1=ANN-BUS
control panel. Pressing 2 while viewing Programming Screen #3 will display the History options as
2=HISTORY
3=WALKTEST
shown in the following display:
Programming Screen #3
74
• General Alarm
• General Trouble
• General Supervisory
• General Pre-Discharge
• Pre-Discharge Release 1
• Pre-Discharge Release 2
• General Discharge
• Discharge Release 1
• Discharge Release 2
• AC Loss
• Waterflow Delay
• General Abort Release
• Abort Release Release 1
• Abort Release Release 2
• Future Use
• Future Use
• Future Use
• Input Zone 1
• Input Zone 2
• Input Zone 3
• Input Zone 4
• Input Zone 5
• Input Zone 6
ANN-RLY #
1=TYPE
2=LATCHING
NO
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016