Error code
Flashing of
ERR LED
ASCII hex
0005
5x
0006
6x
0007
7x
0008
8x
0009
9x
000A
10x
000B
11x
000C
12x
000D
13x
RF182C communication module
Operating Instructions, 10/2010
1)
Unknown command
The client is sending an uninterpretable command to the communication module.
Check the XML command
The MDS reported an address error
Field interference on write/read device
The write/read device is receiving interference from its environment.
The distance between two write/read devices is too small and does not correspond
to the configuration guidelines
The connecting cable to the write/read device is defective or too long or does not
comply with the specification
MOBY U: MDS has left the field during communication.
MOBY U: Communication between write/read device and MDS was terminated by
interference (e.g. person/foreign body moving between write/read device and MDS).
Too many transmit errors
The MDS was not able to correctly receive the command or the write data from the
communication module even after several attempts.
The MDS is positioned exactly on the boundary of the transmission window.
Data transmission to the MDS is being affected by external interference.
CRC sending error
The receiver monitor has detected at least one fault during transmission.
Cause same as error 0006
MDS signaling CRC error frequently.
The MDS is positioned exactly on the boundary of the write/read device.
The hardware of the MDS and/or write/read device is defective.
Only during initialization: CRC error during acknowledgment receipt from MDS
Cause same as error 0006
Only during initialization: MDS is unable to perform the initialization command.
MDS is defective.
MOBY U: Memory of MDS cannot be read correctly.
Memory of the MDS cannot be write-accessed.
Memory of the MDS is defective.
EEPROM MDS was written too frequently and has reached the end of its service life
Address error
The address area of the MDS was exceeded.
Check the XML command
The MDS is not the right type.
RF300: Attempted write access to write-protected areas (OTP area)
9.3 Error messages of the RF182C