Error code
Flashing of
ERR LED
ASCII hex
0019
25x
001C
28x
001D
001E
30x
001F
The flashing ERR-LED can be implemented either on the communication module or on the reader.
1)
RF182C communication module
Operating Instructions, 10/2010
1)
Previous command is active or buffer overflow
The user sent a new command to the communication module although the last
command was still active.
Active command can only be terminated with RESET.
•
Two client calls were parameterized with the same parameters
•
Start RESET after error correction
•
When command repetition is used, no data is fetched from the MDS. The data buffer
•
on the communication module has overflowed. MDS data have been lost.
The antenna of the write/read device is turned off. An MDS command to the
communication module was started in this state.
Turn on the antenna with the command "antenna on/off."
•
The antenna is turned on (off) and has received an additional turn-on (turn-off)
•
command.
–
More MDSes are in the transmission window than the SLG is capable of processing
simultaneously.
Only 1 MDS can be processed at a time with a client
•
Error when processing the function
Communication module defective: The communication module receives wrong data
•
during a RESET
–
Running command canceled by RESET
Communication with the MDS was terminated by RESET
•
This error can only be reported if there is a RESET
•
9.3 Error messages of the RF182C
Description
Error messages
75