15.1.3 IPM (Power Transistor) Prevention Control
Overheating Prevention Control
1
When the IPM temperature rises to 120°C, compressor operation will stop immediately.
2
Compressor operation restarts after 3 minutes the temperature decreases to 110°C.
3
If this condition repeats continuously 4 times within 30 minutes, timer LED will be blinking ("F96" is indicated).
DC Peak Current Control
1
When electric current to IPM exceeds set value of 20 A, the compressor will stop operate. Then, operation
will restart after 3 minutes.
2
If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will
restart after 1 minute.
3
If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after
1 minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer
LED will be blinking ("F99" is indicated).
15.1.4 Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
If compressor discharge temperature exceeds 107°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. ("F97" is indicated.)
15.1.5 Low Pressure Prevention Control (Gas Leakage Detection)
Control start conditions
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.75A and 0.95A.
o
During Cooling and Dry operations:
o
Indoor suction temperature - indoor piping temperature is below 4°C.
During Heating operations :
o
Indoor piping temperature - indoor suction is under 5°C.
Control contents
Compressor stops (and restart after 3 minutes).
o
If the conditions above happen 2 times within 20 minutes, the unit will:
o
Stop operation
Timer LED blinks and "F91" indicated.
15.1.6 Low Frequency Protection Control 1
When the compressor operate at frequency lower than 24 Hz continued for 240 minutes, the operation frequency
will be changed to 23 Hz for 2 minutes.
15.1.7 Low Frequency Protection Control 2
When all the below conditions comply, the compressor frequency will change to lower frequency.
Indoor intake air (°C)
Outdoor air (°C)
Indoor heat exchanger (°C)
103°C
(107°C)
99°C
(105°C)
96°C
(95°C)
Comp. temperature
(Comp. Discharge temperature)
Temperature, T, for:
Compressor = OFF
Compressor Frequency
Reduce
Compressor Frequency
Maintain
Free
Cooling/Dry
T < 14 or T ≥ 30
T < 13 or T ≥ 38
T < 30
87
92°C
91°C
90°C
(85°C)
Heating
T < 14 or T ≥ 28
T < 4 or T ≥ 24
T ≥ 0