− − − − Air Purifying Filter features a deodorizing function that removes unpleasant odors from the air. · Installation Work Improvement − − − − Long piping up to 10 m (CS-VA70KE / CS-VA90KE) − − − − Long piping up to 15 m (CS-VA120KE) · Quality Improvement −...
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 4.2. CU-VA70KE / CU-VA90KE (OUTDOOR UNIT) Panasonic 2-way valve at Liquid side 3-way valve at Gas side 4.3. CU-VA120KE(OUTDOOR UNIT) 2-way valve at Liquid side 3-way valve at Gas side...
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 7 Wiring Diagram POWER SUPPLY CORD DISPLAY LAMP CN-DISP (W) W W W W WIRELESS REMOTE PUMP CN-DISP (W) AUTO CONTROL DOWN SW (TEST RUN) ELECTRONIC ELECTRONIC CONTROLLER REMOTE CONTROLLER CONTROL NO.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 8 Operation Details 8.1. COOLING MODE OPERATION Cooling in operation according to the remote control setting. 8.1.1. Time Delay Safety Control (3 minutes) · When the compressor is stopped by Power Switch, Remote Control or when there is a power failure, it restarts after 3 minutes when the Power Switch, Remote Control is turned ON or when the power supply is resumed.
Page 20
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 8.1.6. Automatic Fan Speed Mode When Automatic Fan Speed is selected on the remote control during cooling operation. · Fan speed rotates in the range of Hi to Me.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 8.2. SOFT DRY MODE OPERATION · The unit performs cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and then Soft Dry operation will start.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 8.3. HEATING MODE OPERATION Heating in operation according to the remote control setting. 8.3.1. Time Delay Safety Control · When the compressor is stopped by Power Switch, Remote Control or when there is a power failure, it restarts after 3 minutes when the Power Switch, Remote Control is turned ON or the power supply is resumed.
Page 24
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 8.3.6. Automatic Fan Speed Mode When Automatic Fan Speed is selected on the remote control during heating operation. · Fan speed rotates in the range of Me → SLo according to the heat exchanger temperature.
Page 25
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 8.3.8. Deicing Control Deice operates to prevent frosting at outdoor heat exchanger. · Normal Deicing Deice operation detection commences after 30 minutes of Heating operation or 60 minutes after previous deice operation.If the TRS (Thermal Reed Switch) senses the outdoor piping temperature drops to -3 °C (TRS CLOSE)
Page 26
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 8.3.9. Normal Deicing Time Diagram 8.3.10. Overload Deicing Time Diagram...
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 8.4. AUTOMATIC MODE OPARATION 8.4.1. Standard for Determining Operation Mode 1. Indoor fan operates at SLo fan speed for 20 seconds. 2. After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 8.6. AUTO RESTART CONTROL · If there is a power failure, operation will be restarted automatically when the power is resumed. It will start with the previous operation mode and airflow direction.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 8.8. AIRFLOW DIRECTION CONTROL 8.8.1. Airflow Direction Auto-Control · When set to Airflow Direction Auto-Control on the remote control, the louver swings up and down as shown in the diagram.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 9 Installation And Servicing Air Conditioner Using R410A 9.1. OUTLINE 9.1.1. About R410A Refrigerant 1. Converting air conditioners to R410A Since it was declared in 1974 that chlorofluorocarbons (CFC), hydro chlorofluorocarbons (HCFC) and other substances pose a destructive danger to the ozone layer in the earth´s upper stratosphere (20 to 40 km above the earth), measures have been...
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE conventional refrigerating machine oils. Also, these synthetic oils will degrade if mixed with mineral oil or alkylbenzene, causing clogging in capillary tubes or compressor malfunction. Do not mix them under any circumstances.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 9.2.2. R410A Tools 1. Copper tube gauge for clearance adjustment (used when flaring with the conventional flaring tool (clutch type)) · This gauge makes it easy to set the clearance for the copper tube to 1.0-1.5 mm from the clamp bar of the flaring tool.
Page 33
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 5. Charging hose · The pressure resistance of the charging hose has been raised to match the higher pressure of R410A. The hose material has also been changed to suit HFC use, and the size of the fitting has been changed to match the manifold ports.
Page 34
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 9. Refrigerant cylinders · The R410A cylinders are labeled with the refrigerant name, and the coating color of the cylinder protector is pink, which is the color stipulated by ARI of the U.S.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 9.3. REFRIGERANT PIPING WORK 9.3.1. Piping Materials It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg/10 m. Do not use pipes that are crushed, deformed, or discolored (especially the inside surface).
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE b. Take special care when doing piping work on rainy days. The entering of moisture will degrade the refrigerating machine oil, and lead to malfunctions in the equipment. c. Complete all pipe connections in as short a time as possible. If the pipe must be left standing for a long time after removing the seal, it must be thoroughly purged with nitrogen, or dried with a vacuum pump.
Page 38
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE · Press the TEST RUN button on the indoor unit, and allow preliminary operation for 5-6 minutes. (TEST RUN mode) · After stopping the operation, let the unit sit for about 3 minutes, then close the 2-way valve by turning the valve stem in the clockwise direction.
Page 39
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 7. Open the valve of the refrigerant cylinder, then open the charging valve slightly and close it. Next, press the check valve of the manifold gauge and purge the air. (2)(4) (Watch the liquid refrigerant closely at this point.) 8.
Page 40
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 6. After taking the steps above, keep the nitrogen gas flowing until the piping cools down to a certain extent (i.e. temperature at which pipes are touchable with finger).
1/2” 1/4” *1.The additional gas charge is unnecessary up to the Max. piping length. (CS-VA70KE, CS-VA90KE) *2. The above models (CS-VA120KE) will be installed at a 15 m (max) distance. The refrigerant should be added 150g. ( 15m - 10m ) x 30g = 150g...
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 11.1. EVACUATION OF INSTALLATION WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO If air remains in the indoor unit and refrigeration pipes, it will EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES affect the compressor, reduce the cooling capacity, and could in the following procedure.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 11.2. PUMPING DOWN Procedure: 9. Disconnect the charge set, and mount the 2-way and 3- way valves stem caps and the service port caps. 1. Confirm that both the 2-way and 3-way valves are set to ∙...
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 11.3. EVACUATION OF RE-INSTALLATION WHEN RE-INSTALLING AN AIR CONDITIONER, BE SURE If air remains in the indoor unit and refrigeration pipes, it will TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND affect the compressor, reduce the cooling capacity, and could PIPES in the following procedure.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 11.4. BALANCE REFRIGERANT OF THE 2-WAY, 3-WAY VALVE (Lack of refrigerant in the refrigeration cycle) Procedure: 1. Confirm that both the 2-way and 3-way valve are set to the open position.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 11.5. EVACUATION (No refrigerant in the refrigeration cycle) Procedure: 1. Connect the vacuum pump adapter and vacuum pump to the charge sets centre hose. 2. Evacuation for approximately one hour.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 12 Servicing Information 12.1. INSPECTION POINTS FOR THE INDOOR ELECTRONIC CONTROLLER 1. The Electronic Controller, a Signal Receiver and an Indicator can be seen by removing the Front Grille and Control Board Cover, as shown in the Fig 1.
Page 50
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 3. Remove the Fan Motor Loosen the Fan Motor securing screw at the junction with Cross Flow Fan. (Fig. 5) Fig. 5 Remove the particular piece and the Fan Motor can be taken off as shown in Fig.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 4. To fix the Indoor Fan Motor, ensure that the Fan Motor securing screw is positioned at the rear side and the Fan Motor lead wire is positioned parallelly with the Fan Motor. (Fig 8.) Fig.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 4. Take off the mounting tab at the left of the Heat Exchanger, pull the Heat Exchanger forward (left side) and remove the Cross Flow Fan. (Fig 11.) Fig. 11 12.4.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 12.6. CHANGING THE WIRELESS REMOTE CONTROL TRANSMISSION CODE When two indoor units are installed in the same room, in order to prevent operating errors caused by using two remote controls, set up the remote control [ B ←→...
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 13.1. RELATIONSHIP BETWEEN THE CONDITION OF THE AIR CONDITIONER AND GAS PRESSURE AND ELECTRIC CURRENT Condition of the air conditioner Cooling Mode Heating Mode Low Pressure High Pressure Electric current...
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 15 Electronic Circuit Diagram 15.1. HOW TO USE ELECTRONIC CIRCUIT DIAGRAM Before the circuit diagram, read the following carefully. Voltage measurement voltage has been measured with a digital tester when the indoor fan is set at high fan speed under the following conditions without setting the timer.
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 15.5. TIMER TABLE Name Time Test Mode (When Remarks test point Short- circulated) Sleep Mode Waiting 1 hr. 6 sec. Sleep Mode Operation 8 hrs. 48 sec. 1 h.
Page 68
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 17.1.2. Replacement Parts List Ref.No. CS-VA70KE / CS-VA90KE DESCRIPTION & NAME Q’TY Remarks CWD50C202 CHASSY COMPLETE G G G G CWA98244 FAN MOTOR CWH02C053 CROSS FLOW FAN COMPLETE CWH4580304...
Page 70
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 17.2.2. Replacement Parts List Ref. No. CS-VA120KE DESCRIPTION & NAME Q’TY Remarks CWD50C202 CHASSY COMPLETE G G G G CWA98244 FAN MOTOR CWH02C053 CROSS-FLOW FAN CWH4580304 SCREW-CROSSFLOW FAN CWH64K007 BEARING ASS’Y...
Page 74
CS-VA70KE / CU-VA70KE / CS-VA90KE / CU-VA90KE / CS-VA120KE / CU-VA120KE 17.4.2. Replacement Parts List Ref. No. CU-VA120KE DESCRIPTION & NAME Q’TY Remarks CWD50K612B CHASSY COMPLETE CWD54260 BRACKET FAN NOTOR CWH4580399 SCREW-FAN MOTOR BRACKET G G G G CWA95230 FAN MOTOR...