Non-stop heating deice operation is prohibited when any of the following condition is met
Protection control that limit capacity.
o
Aluminium electric heater (HEATCHARGE) temperature sensor abnormal.
o
Aluminium electric heater (HEATCHARGE) cycle abnormal.
o
Outdoor pipe temperature sensor 2 abnormal.
o
The outdoor temperature range falls under -30°C.
o
Deice stop condition
Outdoor air temperature is more than 9°C
o
15.3.6 Base Pan Heater Protection Control
Base pan heater it installed inside to the outdoor unit at base pan. It is for quickly melted ice at base pan area.
When outdoor air temperature is 4°C, Base pan heater operation starts.
If the temperature is more than 6°C, base pan heater operation stop.
15.3.7 Aluminium Electric Heater 3-Way Valve Control
Aluminium electric heater 3-way valve temperature sensor is used for the abnormality determination of aluminium
electric heater 3-way valve cycle.
Control condition:
Aluminium electric heater 3-way valve temperature sensor
Outdoor operation
Aluminium electric heater 3-way valve temperature sensor is disconnected or short circuit continuously in 5sec.
Error code H80 will be appear.
Indoor operation
If aluminium electric heater 3-way valve temperature sensor error code (H80) is received, after powerful
operation OFF in 2 minute, the operation will be continues.
If abnormality of aluminium electric heater 3-way valve temperature sensor error code (H80) is received from
outdoor once again, the operation will be continued in the stage of flashing timer.
However, if H80 doesn't come from outdoor within 10 sec after outdoor power turned ON, abnormality will be
cancelled.
Thermo OFF delay - Aluminium electric heater 3-way valve control
Aluminum electric heater 3-way valve will open before thermo OFF to change the room temperature during thermo
OFF and to reduce loss during thermo ON >.
Start condition
1
Heater ON or compressor ON.
2
Control area is continued more than 90 second.
3
Not in protection operating of capacity limit.
4
Not in de-icing operation.
5
Temperature of outdoor piping temperature is greater than or equal to -3°C.
6
Indoor piping temperature is greater than or equal to 35°C.
7
More than 5 hours after deice completed.
8
After more than 20 minute.
9
Compressor frequency (Hz) is the control area as below.
Outdoor air temperature
4°C
OFF
ON
Outdoor air temperature
91
6°C