D9412G/D7412G | Operation & Installation Guide |

Figure 4: Reset Pin

Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
32
RED
POWER +
YELLOW
DATA BUS A
31
30
GREEN
DATA BUS B
29
BLACK
COMMON
1 - Reset pin locked (closed).
2 - Reset pin normal (open).
3.6

Finishing the Installation

If not already complete, make the earth ground
connection to Terminal 10 and lock the reset pin in the
closed position.
3.6. 1

Charge the Battery While Finishing

Connect the battery and then the transformer so the
panel can charge the battery while the installation is
being completed. See Section 4.0 Power Supply for
instructions.
On-board Buzzer Sounds at Power Up and Reset:
The system performs a series of self-diagnostic tests of
hardware, software, and program at power up and at
reset. The buzzer on the panel sounds during the tests.
The self-diagnostics takes approximately 1 second to 3
seconds to complete.
If the panel fails any test, the buzzer continues sounding
and a System Trouble message appears at the command
centers. See Problems Found During Self Diagnostics in the
D9412G/D7412G/D7212G Installation and Troubleshooting
Quick Reference Guide for a description of each system
trouble message.
Touch Terminal 10 First: If the on-board buzzer sounds
briefly when the panel is touched, any static charge that
may be carried is being discharged to the panel. The
panel may generate Watchdog Reset and/or Param Fail
events. See Watchdog Reset Reports in the D9412G/7412G/
D7212G Installation and Troubleshooting Quick Reference
Guide for a description of these events. Always touch
Terminal 10, the panel's earth ground connection, before
beginning work on the panel.
Bosch Security Systems | 10/03 | 43488E
3.0 Installation
3.6.2
Install and wire detection devices and command centers
at their locations throughout the premises. Do not make
the connections at the panel end of the wiring yet.
Section 7.0 On-board Points contains instructions for
wiring the on-board points to detection devices. Section
10.0 Arming Devices contains instructions for wiring the
1
command centers.
Instructions for wiring the off-board point POPIT
sensor loops are found in the instructions packaged with
the POPIT modules.
2
3.6.3
1. Power down the unit by unplugging the transformer
and disconnecting the battery. Always power down
the unit when installing modules or relays, or when
making wiring connections to the panel.
2. Install and wire any modules required for the
installation as described in the module's installation
instructions.
Instructions for the D8125 POPEX Module,
D8128D OctoPOPIT Module, D8129 OctoRelay
Module, D811 Arm Status Relay Module, and D928
Dual Phone Line Switcher appear in this guide.
See Section 8.0 Off-board Points for D8125 and
D8128D instructions. See Section 9.0 Off-board Relays
for D8129 and D811 instructions. See Section 6.12
D928 Dual Phone Line Switcher for instructions for
the D928.
3. If using the power outputs at Terminals 7 or 8,
install a D136 relay in the appropriate sockets. See
Section 5.4 Programmable Power Outputs Terminals for
instructions.
4. If using a ground start phone system, insert a D136
relay in the ground start check socket and set the
ground start pin in the ground start position. See
Section 6.11 Ground Start for more information.
3.6.4
See Section 6.0 Telephone Connections. If connecting the
panel to a ground start phone system, install a D136
relay (Section 3.6.3 Install Modules and Relays).
3.6.5
Connect the on-board points and command center
wiring to the system. See Section 7.0 On-board Points and
Section 10.0 Arming Devices for instructions.

Install and Wire Detection Devices

Install Modules and Relays

Make the Telephone Connections

Connect the On-board Points and Command
Centers
EN | 19