Troubleshooting by Remote Controller

2. Troubleshooting by Remote Controller

2.1

Mode ChangeOver

The following modes can be selected by using the [Inspection/Test Operation] button on the
remote control.
Indoor unit settings can be made
• Filter sign time
• Airflow direction
• Others
Depress the Inspection/Test Operation button
for more than 4 seconds.
Press the Inspection/Test Operation
button once.
Following codes can be checked.
• Error codes
• Indoor model code
• Outdoor model code
Service Diagnosis
Depress the Inspection/Test Operation button
for more than 4 seconds.
Field
setting
mode
Normal
mode
After 10 seconds
Inspection
mode
Press the Inspection/Test Operation
button once.
Service data can be obtained.
• Error code history
Service
• Temperature data of various sections
mode
Service settings can be made.
• Forced fan ON
• Airflow direction/volume setting
Press the Inspection/Test Operation button once.
Press the Inspection/Test Operation button once.
Or after 30 minutes
Test
operation
Thermostat is forcibly turned ON.
mode