Using Heater Burnout Alarm (HBA)

3-10-3 Setup

Operation Procedure
Moving to the advanced function setting level
1,2,3...
Operation level
PV/SP
C
25
100
Initial setting level
Input type
in-t
5
amoV
-169
Advanced function setting level
Move to advanced
init
function setting
level
off
HB ON/OFF
hbu
on
46
To activate the heater burnout alarm, set the "HB ON/OFF" parameter
(advanced function setting level) to "ON" and the heater burnout set value in
the "heater burnout detection" parameter (adjustment level).
In this example, let's set the "heater burnout detection" parameter to "2.5".
The default of the "heater burnout" parameter is already "ON", so set the
"heater burnout detection" parameter.
1. Move to the advanced function setting level.
Press the
key for at least three seconds to move from the "operation
level" to the "initial setting level".
2. Then move to "advanced function setting level" by pressing the
key to enter the password (" − 169"), and move from the "ini-
3. Press the
tial setting level" to the "advanced function setting level".
The top parameter in the "advanced function setting level" is displayed.
4. Select the "HB ON/OFF" parameter by pressing the
Make sure that this parameter is set to "ON" (default).
Next, let's set the "heater current value monitor" parameter.
Section 3-10
key.
key.