Executing Heating/Cooling Control
Output
0
4-4-2
Settings
Setting heating/cooling control
Operation Procedure
1,2,3...
Initial setting level
Standard/
heating and
cooling
Setting cooling coefficient
Operation Procedure
1,2,3...
Adjustment level
Cooling
c-5c
coefficient
1.00
c-5c
10.00
62
Dead band:
dead band width = positive
Heating side
Cooling side
Set point
To set heating/cooling control, set the "standard or heating/cooling", "cooling
coefficient" and "dead band" parameters.
"Standard or heating/cooling" = "heating and cooling"
1. Press the
level" to the "initial setting level".
2. Select "heating/cooling control" in the "initial setting level".
stnd: Standard control
h-c: Heating/cooling control
Cooling coefficient = 10
1. Select "cooling coefficient" in the "adjustment level".
In this example, set the parameter to "10".
2. Press the
The setting range is 0.01 to 99.99.
Output
Heating side
PV
0
key for at least three seconds to move from the "operation
or
key to set the parameter to "10.00".
Section 4-4
Overlap band:
dead band width = negative
Cooling side
PV
Set point