Adjustment Level
Manual reset value
Function
Setting
See
Hysteresis (OUT1)
Hysteresis (OUT2)
Function
Setting
See
• This parameter sets the required manipulated variable to remove offset
during stabilization of P or PD control.
Setting Range
0.0 to 100.0
■ Related parameters
"PID ON/OFF" (initial setting level)
"Integral time" (adjustment level)
This parameter sets the hysteresis for ensuring stable operation at ON/OFF
switching.
• In a standard control, use the "hysteresis (OUT1)" parameter. The "hys-
teresis (OUT2)" parameter cannot be used.
• In a heating/cooling control, the hysteresis can be set independently for
heating/cooling. Use the "hysteresis (OUT1)" parameter to set the control
output 1 side hysteresis, and use the "hysteresis (OUT2)" parameter to
set the control output 2 side hysteresis.
Setting Range
0.1 to 999.9
Note Set "none" as the unit for Controllers with Analog Inputs.
■ Related parameters
"PID ON/OFF" (initial setting level)
The control must be standard control
and 2-PID control. The "integral time"
parameter must be set to "0".
Unit
Default
%
50.0
The control must be ON/OFF control.
Unit
Default
EU
1.0
Section 5-4
93