Advanced Function Setting Level
MV upper limit
MV lower limit
Function
Setting
See
114
• The "MV upper limit" and "MV lower limit" parameters set the upper and
lower limits of the manipulated variable. When the manipulated variable
calculated by the E5AZ/E5EZ exceeds the upper- or lower-limit value, the
upper or lower limit set value becomes the output level.
• MV upper limit
The setting ranges during standard control and heating/control output 2
control are different.
The manipulated variable at the cooling side during heating/cooling con-
trol is expressed as a negative value.
Control Method
Standard
Heating/cooling
• MV lower limit
The setting ranges during standard control and heating/cooling control
are different.
The manipulated variable at the control output 2 side during heating/cool-
ing control is expressed as a negative value.
Control Method
Standard
Heating/cooling
■ Related parameters
"PID ON/OFF" (initial setting level)
"ST" (initial setting level)
The control must be 2-PID control,
and the "ST" parameter must be set
to "OFF".
Setting Range
MV lower limit +0.1 to 105.0
0.0 to 105.0
Setting Range
−5.0 to MV upper limit −0.1
−105.0 to 0.0
Section 5-6
Unit
Default
%
105.0
%
105.0
Unit
Default
−5.0
%
−105.0
%