Omron E5AZ User Manual page 121

Digital temperature controller
Hide thumbs Also See for E5AZ:
Table of Contents

Advertisement

Initial Setting Level
Alarm 2 type
a l t 3
Alarm 3 type
Function
Setting
102
• Select one of the following alarm 2, 3 types:
Deviation/Deviation range/Absolute value
Alarm Type
Set
Value
0
Alarm function OFF
1
Upper- and lower-limit
(deviation)
(See note 1.)
2
Upper-limit (deviation)
3
Lower-limit (deviation)
4
Upper- and lower-limit
range (deviation)
(See note 1.)
5
Upper- and lower-limit
alarm with standby
sequence (deviation)
(See note 1.)
6
Upper-limit alarm with
standby sequence
(deviation)
7
Lower-limit alarm with
standby sequence
(deviation)
8
Absolute-value upper-limit
9
Absolute-value lower-limit
10
Absolute-value upper-limit
with standby sequence
11
Absolute-value lower-limit
with standby sequence
The alarm 2, 3 type must be sup-
ported.
The control must be set to standard
control.
Alarm Output Operation
When alarm value
When alarm value X
X is positive
Output OFF
(See note 2.)
L H
ON
OFF
SP
X
ON
ON
OFF
OFF
SP
X
ON
OFF
SP
(See note 3.)
L H
ON
OFF
SP
(See note 4.)
L H
ON
OFF
SP
(See note 5.)
X
ON
OFF
SP
X
ON
ON
OFF
OFF
SP
X
ON
ON
OFF
OFF
0
X
ON
ON
OFF
OFF
0
X
ON
OFF
0
X
ON
ON
OFF
OFF
0
Section 5-5
is negative
X
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
SP
X
0
X
0
X
ON
OFF
0
X
0