Operation Level
PV
Function
Monitor
See
PV/SP
Function
Monitor
See
m-sp
Multi-SP (set point 0 to 3)
Function
The process value is displayed on the No.1 display, and nothing is displayed
(blank) on the No.2 display.
Process
Input indication range (See page 133.)
Value
During temperature input, the decimal point position depends on the currently
selected sensor, and during analog input, it depends on the "decimal point"
parameter setting.
■ Related parameters
"Input type" (initial setting level)
"Set point upper limit" "Set point lower limit" (initial setting level)
The process value is displayed on the No.1 display, and the set point is dis-
played on the No.2 display.
Process
Input indication range (See page 133.)
Value
Set Point
Set point lower limit to set point upper limit
During temperature input, the decimal point position depends on the currently
selected sensor, and during analog input, it depends on the "decimal point"
parameter setting.
Refer to the PV parameter.
Multi-SP allows you to set up to four set points (SP 0 to 3) in adjustment level.
These can be switched by operating the keys on the front panel or by external
input signals (event input). In the parameter, enter set points 0 to 3.
The "additional PV display" parame-
ter must be set to "ON".
Monitor Range
Monitor Range
Setting Range
The "multi-SP uses" parameter must
be set to "ON".
Section 5-3
Unit
EU
Unit
EU
Unit
EU
79