Omron E5AZ User Manual page 118

Digital temperature controller
Hide thumbs Also See for E5AZ:
Table of Contents

Advertisement

Initial Setting Level
PID ON/OFF
Function
Setting
See
s-hc
Standard or heating/cooling
Function
Setting
See
• This parameter selects 2-PID control or ON/OFF control.
• The AT and ST tuning functions can be used in 2-PID control.
Setting Range
pid: 2-PID /onof: ON/OFF
■ Related parameters
"AT execute/cancel" "Manual reset" "Hysteresis (OUT1)" "Hysteresis (OUT2)"
(adjustment level)
"ST stable range" (advanced function setting level)
• This parameter selects standard control or heating/cooling control.
• When heating/cooling control is selected, the alarm 3 output terminal
"ALM3" is used for control output 2 side output. So, alarm 3 cannot be
used.
Setting Range
stnd: Standard /h-c: Heating/cooling
■ Related parameters
"MV monitor (OUT1)" "MV monitor (OUT2)" (operation level)
"Alarm value" "Alarm value upper limit 3" "Alarm value lower limit 3" (operation
level)
"Hysteresis (OUT2)" "Cooling coefficient" "Dead band" (adjustment level)
"Control period (OUT2)" (initial setting level)
"Alarm 3 type" (initial setting level)
"Alarm 3 hysteresis" "Alarm 3 open in alarm" (advanced function setting level)
Section 5-5
Default
onof
Default