3.3 Specifications

.
The UPS nameplate displays the rated kVA as well as nominal voltages and currents. The nameplate is located on
the backside of the Bypass module door.
Rated output
Power
1200kVA / 1200kW
1600kVA / 1600kW
2000kVA / 2000kW
UPS
Width
[kVA]
[in. (mm)]
133.9
1200
(3,400)
169.3
1600
(4,300)
192.9
2000
(4,900)
18
Table 3–1 Power Specifications
Input voltage
3 phase / 3 wire
480V
480V
480V
Table 3–2 UPS Cabinet Information
Depth
Height
[in. (mm)]
[in. (mm)]
35.4
81.0
(900)
(2,058)
81.0
35.4
(900)
(2,058)
81.0
35.4
(900)
(2,058)
G9400 480V 1200-2000kVA Installation and Operation Manual 203078-001
Bypass input voltage
3 phase / 3 wire
480V
480V
480V
Typ. Heating
Net Weight
at 100% load
[lbs. (kg)]
[kBTU/h]
7,275
(3,300)
9,750
(4,420)
11,470
(5,200)
Output voltage
3 phase / 3 wire
480V
480V
480V
Cable
Knockout
TOP,
126.6
BOTTOM,
LEFT SIDE
TOP,
168.8
BOTTOM,
TOP,
211.1
BOTTOM,

Advertisement