Specifications; Specifications - 5000 Series Ups 3P-3W 480V; 2W 120V - Toshiba 5000 Series Installation And Operation Manual

Industrial ups. 3-phase, 480vin - single phase, 120vout
Hide thumbs Also See for 5000 Series:
Table of Contents

Advertisement

11

Specifications

11.1
Specifications – 5000 Series UPS 3P–3W 480V
Specifications
Input
KVA rating
Phase/Line
Voltage
Frequency
Input power factor
THD
Output
Phase/Line
Voltage
Voltage adjustable range
Frequency
Rated load power factor
Admissible output crest factor
Frequency Regulation
Frequency Slew Rate
Frequency Synchronous Range
Voltage Regulation
Regulation time
Voltage distortion rate / THD
Overload
Transient Response
System Efficiency
Battery
Battery Nominal Voltage
Battery Minimum Voltage
Battery Float Voltage
Ripple Voltage w/o Batteries
Maximum Re-charge Current
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001
TABLE 11.1: % 5000 SERIES 3P1 SPECIFICATIONS
5000 Series Industrial Duty 3-Phase In/1-Phase Out
15kVA
84.3% @ 100% Load 82.6% @ 100% Load
, 1P–2W 120V
in
Value
30kVA
3PH-3W + Ground
480 V (+10% to -10%)
(-15% with Batteries in Parallel)
60 Hz (±5 Hz)
>0.95
< 6% @ 100% Load
1PH-2W + Ground
120 V
±5% of Rated Voltage in Increments of 1 V
60 Hz
0.9 lagging
3.0
±0.01% in free running mode
1.0 Hz/sec
±0.5 Hz, ±1 Hz, ±1.5 Hz
±3% (100% Linear Load)
Regulation time to +/-1 % <60 msec
Regulation time to +/-3 % <20 msec
100% Linear load: ≤3%
100% Non-linear load: ≤5%
110-125% for 10 min.,
150% for 60 sec
±2% Max with a 100% Step Loads,
±1.5% Max with Loss/Return AC input,
±2% Max when load transfers To/From Bypass
120 Vdc
105 Vdc (@1.75V/Cell) (Default)
96 Vdc (@1.6V/Cell)
135 Vdc
< 0.2% of DC Voltage
30 A
out
50 kVA
83.1% @ 100% Load
41

Advertisement

Table of Contents
loading

Table of Contents